Today when I arrived I met with Tyler and he brought me to the kitchen. The temperature in the kitchen was 78deg and the humidity was elevated. This kitchen is served by a twinned split system. The return and supply temps at the furnaces were checked. The outdoor condensers are just outside the kitchen and are labeled #3 and #4. The compressor amp draw on condenser #3 was in range. The compressor amp draw on condenser #4 was out of range at 24amps. The condenser was blanketed with cottonwood that was preventing the system from expelling heat. Both condensers were washed and dried, the capacitor for the replaced compressor in unit #4 was checked and then they were restarted. The compressor in system #4 amp draw fell back into proper range at 18amps and the system returned to cooling. The temp split was checked at the first ceiling register and was 60 deg with a return temp of 78. Went outside and reattached a outdoor fan motor reversing wire that I noticed had a broke