Arrived onsite for ac maintenance. Confirmed operation of the system. Changed filters. Cleaned outdoor coil. Cleared condensate trap. Measure temperature drop up to 14 degrees. Outside temperature was 46 degrees which may affect cooling capacity. Pressures for 410a 80/176 with 9 degree sub cooling.