Perform the leak test for the Fujitsu VRF system, went through all of the flare connections on all eight indoor units. All of the flare connections and ProPress connections are in good condition and are not leaking. Went through all of the connections at the separation tubes for each zone and confirmed that they are not leaking. Dismantled the condenser on the roof and found that the bottom rows of the condenser or severely covered in oil and the bottom of the unit is covered in oil. The condenser coil is leaking and will need to be replaced.