Upon arrival I began the furnace tune up. This house has 2 systems total. One controls the left side of the home and the other, the right side of the home. I am starting with the left hand side unit. I did a static pressure test on this unit. It has a max rating of .8 and the unit is testing at .85 which is above the max. Customer is aware and doesn’t wish to make any further changes with the static pressure on either unit. We have made airflow improvements to both systems. The right hand side unit has a static rating of .8 also but it is testing at .78 which is high but not failing. I checked the running amps on the inducer and blower motor on both units. The inducer motors were both within specs. The blower motor on both units were overamping the rating of 6.6amps. They were both amping around 7.5amps and this is due to the high static pressure. Everything else checked out with both units. They are both safe to operate at this time. If you have any questions or concerns please feel