Steve R.

Steve R.


Job Checkin

12-15-25 Father Quiggly building classroom 105 The heating temperature is really erratic showing spikes on the energy management screen. We pulled the filter, which had some heavy debris on it, but not clogged. The temperature did even out on the screen. We’ll see how it goes tomorrow morning. Classroom 148 The temperature on the monitor output is reading 140°F. However, the room is very cold. Can we check the room? The ceiling is real hot. I pulled the filter. It wasn’t dirty, but it came out real easy. Doug and I located the return ductwork, and for whatever reason it was capped with cardboard and foil tape. We removed the cardboard and tape you can actually hear the airflow coming out of the registers at this time and there was a lot of movement on objects in the room mostly the disco balls We checked the monitor temperature seem a lot more in control The furnace for the sanctuary south This is a sterling/trane duct heater Ignition module was indicating a grounded flame sens