Arrived for ac check today started at furnace and checked static pressure, it’s running over the max rating. Blower wheel has some dust build up on it. The capacitor for the blower motor is out of spec. The filter was very dirty so I replaced it. The motor running amps are a little high. There is a 22 degree temp split. At the outdoor condensing unit compressor and fan amps are good. The capacitor tested out of spec. The refrigerant levels are showing off. The ducts were very dirty. My field supervisor was with me on this call and got you set up for duct cleaning, blower clean, and air purification. I replaced both capacitors, and set up smart at sensors. System is running upon departure. Thanks for choosing LBA.