Upon arrival I began by cleaning the outdoor unit. Once cleaned I connected by refrigerant gauges up to the unit to check the charge. The refrigerant charge looks good today. My subcooling target was spot on. I also checked the running amps on the compressor and fan motor outside and both are testing within manufacturer specifications. I also checked the dual run capacitor which is size 40/10mfd and both sides were within specs. I then moved inside to checked the running amps in the blower motor which was within specs as well. The unit is draining properly. Next, I checked the static pressure which is rated for a max of .8 and it testing within specs at .35 which is passing. If you have any questions or concerns please feel free to contact us! Your LBA Technician, Tyler Rickard P.S. No payment was due for todays visit, it was covered with your membership. Have a great week!