Today I arrived at 12:28 and spoke with Sheri. The room that unit#11 serves was humid. I checked the temperatures and the cooling functions. The unit was jumped out and operated until the return temp was 70deg. Currently today’s temperature is 77degf with 64% humidity. The equipment is functioning and bring the temperature down to 74 which is where the thermostat was set. Due to the high humidity load today I recommended setting the thermostat at 72deg to start with to allow the system to run longer which will remove the humidity under today’s conditions. I will relay this information to Steve. Thank you, Jon Tech notes: Lennox rtu#11, KGA090S4BH3G//5613H01903, DT 16, 64% rh, 77degf ambient.