8-13-25 Upstairs meeting room Relocated the existing thermostat from the west wall to the south wall. Then test it for proper operation. Paul Skehen Office stays extremely cold. Found the VAV box damper control was not completely closing when there was no call for cooling it. Only close to about 3/4. I made adjustments to the linkage and the location of the damper drive motor. Ran the system by the thermostat system checked out good and working. Upstairs west hallway is cold. The VAV box for this system is in the insurance brokers office. This is there’s actually a 12 inch damper going into the hallway and the damper control is broken. The only way to fix this is to replace the box itself. I will get a quote together to do that. Stewart title office downstairs SW This office is also cold. There is a 12 inch register that is no damper and it dumps a lot of AC into the space I take to modify this system. I will take care of that on a separate ticket.