Went for an AC inspection today for two systems. Filters got changed. Static pressure passed for both systems. Temperature splits passed for both system. Both indoor coils were clean and rust free. Blower motor amperage passed. Outdoor units got washed. Refrigerant pressures met factory specifications for both. Compressor and fan motor amperage passed for both. The smaller system had a bad capacitor, so I replaced it. The bigger systems capacitor passed. Both ACs are up and running upon completion. Thank you for choosing LBA services! Estimate