Arrived onsite for water leaking from the ac system. Performed diagnostic Confirmed the condensate line is not clogged. Poured water down the drain without issues. Tenant confirmed the filter had recently been changed. Inspected evaporator coil and found the it freezing up. Also determined the drain pan for the evaporator coil is leaking water. System uses phased out R22 refrigerant. Observed the furnace. Blower motor is covered in dust and dirt. The wires are covered in lubricant that has leaked out from the motor due to failed seals. Based on age and condition of the system recommend replacing the system. Provided an estimate to the landlord.
Experiencing cooling issues with your mini-split units in the mid afternoon to early evening? Contact Climate Plus LLC for expert service. We can assist with diagnosing and repairing your system, whether you have one unit with 4 heads or multiple units. Rest easy knowing the cost of service is transparent.