12-28-22 wed<br> Break room and crew bathroom no heat.<br> <br> Spoke to Mike on site<br> Showed me where the split system furnace is for the break room.<br> <br> Visually the furnace control board, hanging from its wires and not mounted.<br> The blower wheel casing is extremely hard to the touch.<br> The blower motor is not hot at all.<br> Set the thermostat for heat. With a cold for heat the control board LED light is not lighting up.<br> When I moved the board the light came on and the burner ignition start it.<br> Burners came on but when call for the blower, motor only hummed.<br> I did check the motor run capacitor, it’s OK.<br> <br> Answer about 15 seconds the LED light on the board tripped off again. <br> <br> The blower motor needs to be replaced also the control board is failing.<br> The ignition glow coil is in pretty bad condition lotta calcium buildup.<br> The inducer motor casing looks that have been quite hot.<br> <br> I spoke to Mike about the quote to replace the uni