4-29-25 Sanctuary is not cooling well Spoke to the pastor upon arrival He showed me where the air handler is is the carrier unit when I got up there I could hear refrigerant flowing through the line and the blower was running. I turned the power power off to the two furnaces however the Freon continue to flow. Got up on the roof and checked the carrier unit found the contact it was stuck in the run. Installed a new contactor 2 pole 24volt Than started the system in ac mode.I found the system was low on refrigerant. One of the service caps was missing and the other three were loose and one did have oil around it. I shut the system down. I have approximately 175, 200 pounds of pressure in the system. I did a leak search at the expansion valves and outside with electronic search. All the piping is pretty much exposed I did not see any oil inside or did not pick up on any leaks. Spoke to the pastor, explained the contacted to him and I need to add refrigerant and approximately $105.00 p