Today (7/10/25) the new contactors, crankcase heater switches and belt was installed and checked. I also replaced the transformer 24v terminal connections the unit returned to normal function with the temperatures and amp draws in their proper range. Once the system was functioning I did notice that the indoor blower wheel and the east condenser fan has a slight vibration. At this time they are both operating well. We will be performing maintenance in a few months and they will be rechecked. Below is the original estimate for reference. Thank you, Jon Tech notes: Odt 87, Lennox rtu unit#10, s/n 0783, blower amps 5.6, comp #1 amps 6.2 (8.2), comp#2 7.5 (10.6), temp diff 17 (74-57), drain clear and draining. ********************************* This is a time plus material estimate for the repair of Unit #10. This Lennox rooftop Lennox rooftop unit #10 (s/n ending 0783) unit serves the dodgeball area. It was diagnosed last week as having two failed contactors and a fai