Went for an ac inspection today. Changed and cleaned filters. Static pressure failed for the Goodman system. Lennox air handler passed static pressure. Blower motor is over amping on York furnace. Evaporator coils are good for the Goodman, but the Lennox coil is rusted. Temp split for the Goodman was 19 and the Lennox was 17. Outside units are clean. Refrigerant levels passed on the Goodman. Fan motor and compressor amperage passed as well. Capacitor passed. Lennox refrigerant levels show a restriction. After performing a diagnostic test. I noticed the filter dryer is causing a restriction. The fan motor amperage is high and compressor amperage is passing. Hard start is still working correctly. Mimi split is cooling correctly. No leaks on the system. Has a clean coil. Thank you for choosing LBA services!