Found the compressor contactor in the outdoor condenser with one of three lugs burnt off with the auxiliary switch and transformer damaged from the arcing. Also found the control voltage transformer in the indoor unit failed from the same damage. Price includes the compressor contactor, contactor auxiliary switch, outdoor unit transformer, indoor unit transformer, wiring repairs and labor. The price quoted is only for the repairs listed. Complete cooling operation cannot be confirmed until the repairs listed are made. Further testing of the system will be preformed after the repairs are completed. Any other repairs if required will be quoted separately. 4-25-25 Today I installed a new contactor and transformer in the outdoor unit also replaced the transformer on the indoor unit. After installing I tested all other functions and found the the compressor in the outdoor unit is short to ground and also needs to be replaced. I have sent the info to rick for estimate on replacement and repl