Arrived for ac check today. Started at furnace and checked static pressure, it is passing. Blower wheel is dirty. Motor amps are good. Blower capacitor is failing. There is a 17 degree temp split. At the condensing unit all pressures and charge look good. Compressor and fan amps are good. The capacitor is failing here too. I rinsed coil clean. Presented to replace both capacitors, that was declined today. System is running upon departure. Thanks for choosing LBA.