Arrived for ac check today. Started at furnace and checked static pressure, it’s running under the max rating. Blower wheel is clean. Motor amps are good. There is a 20 degree temp split. I replaced furnace filter. At the outdoor unit I rinsed coil clean. Pressures and charge look good. Compressor and fan amps are good. Capacitor tested in range. System is running upon departure. Thanks for choosing LBA.