Job Checkin

Completed ac maintenance and inspection. I checked all components and amp draws. I tested airflow and temp splits. I cleaned up condenser coil. Airflow pressure is well over the max recommended airflow pressure. Compressor is starting up pulling 83 amps when the max rating is 70 amps. I noticed customer of current issues. Ac is running for now at departure.