Arrived on site for no cooling. Both air handler and condenser works. Checked pressures, subcooling was 1.1 Temp split was 5.6 degrees. Superheat: 40.4. Checked copper lining for any kinks. Line set looks good. Took a look at evaporator coil. Looks good despite some rust. Unit has a txv. Low pressure was 70.5 High pressure was 227.5. Customer thought about leak test but decided to recharge unit with 3 pounds instead. After charging unit up. The info updated to