10-8-25 Golf course maintenance garage I spoke to John and Cam upon arrival They installed a new LP unit heater and they needed me to check the gas pressure and adjust the burners. I checked the inlet LP gas pressure. I’m getting 11.25”.I need at least 13 to 14”s I went ahead and tried to adjust the gas pressure. The regulator is not cooperating with me. I don’t want. I didn’t wanna bottom it out. I tried running the unit heater with the pressure in the pressure that I had. I need 10 inches and I’m getting about 6.5”and the flames are bouncing all over the place. I spoke to Mike at the shop there and also John they need to have the gas company come out and probably replace that regulator and then I come down and set the pressures as completed for now. The gas is shut off and there is no thermostat wires connected to the unit.