Arrived for ac check today. Started at furnace and checked static pressure, it is failing. I changed furnace filter. Motor amps are good. There is an 18 degree temp split. At the condensing unit all pressures and charge look good. All electrical components are running within manufacturing specs. The contactor is starting to pit. I rinsed coil clean. System is running upon departure. Thanks for choosing LBA.