Went for an AC inspection today. Changed the filter, it was slightly dirty. Static pressure was high on the system. Temperature split between the return and supply duct passed. Evaporator coil is clean and rust free. Outside system is clean. Refrigerant pressures met factory specifications. Compressor and fan motor amperage passed. Capacitor passed as well. Contactor, reversing valve, pressure switch’s are all in good condition. AC is up and running upon completion. Mini split got the filter changed. System is draining fine. No leaks. Thank you for choosing LBA services!