Arrived remedy and in operable system. Started inspection down at the furnace. Checked the systems airflow and found that the system is operating with excessively high static pressure. Check the interior of the system to make sure the evaporator coil is not an air dam. Found that the blower wheel is heavily coded in dust debris. Reached out to a field supervisor to finish the diagnosis on the system static pressure. Went outside and performed diagnostic on the outside unit. Found that the condenser fan is operating but the compressor is not. Through diagnosis was able to find that the condenser capacitor is failed. Installed a new capacitor to continue diagnosis. Verified system refrigerant charge. Spoke with homeowner about repair solutions. With homeowners approval performed the capacitor replacement. System is operational upon departure.