Arrived for ac check today. Started at furnace and checked static pressure, it’s running under the max. Motor amps are good. Blower wheel is collecting dust and needs to be cleaned. There is a 20 degree temp split. I replaced filter. At the condensing unit I cleaned coil. Compressor and fan amps are good. Capacitor tested good. Refrigerant levels are good. Presented blower wheel cleaning and new water heater, options were declined today. Thanks for choosing LBA.