Went for an out on system. Pressure switch wasn’t closing. Did clean port and hose. As well noticed inducer was running weak. Checked capacitor was failing. Did replace and system is up and running. Checked amperage for blower and inducer they are passing. Cleaned flame sensor. Did a combustion test is within range. Inspected heat exchanger no cracks or leaks. Inducer motor is does have some leakage will recommend replacing. Checked temp split and is passing. System is up and running before leaving. Thank you for choosing LBA services-Johann