Arrived for furnace check and ac out. Started at ac and found the capacitor has failed. With approval I replaced capacitor. System started up and is running and cooling properly. For the furnace, static is passing in heat. Carbon monoxide test was 0 ppm. All electrical is running in spec. Heat exchanger has rust in many places. System is running upon departure.