Arrived onsite for no cooling call. Started by confirming call for cooling from the thermostat. Did not hear the blower inside running. Went the the furnace and coil and found no power to the system. Checked the fuse and transformer. Went to the circuit breaker box and found the furnace breaker in the off position. Turn the breaker on and system turned on. Confirmed nothing was over amping and system was cooling.