11-20-25 South RTU Performed the refrigerant leak search on the near the compressor piping there. Looks like there is some residue oil on there. However, I cannot pick up a leak. The system is not completely empty. It’s really not that far off actually refrigerant charge. I cleaned up the pipes and then installed a couple paper towels and a couple areas to see if there’s oil when we come back and do the spring tuneup. While on site, I went ahead and replaced the 2- 1” PVC condensate P traps one on each unit. Both of these traps were cracked and leaking. They were on the estimate for the economize repair however, that’s not gonna be done so I replaced the traps today. I did use new PVC fittings however I used most of the existing pipes upon the roof. This is an estimate repair need to locate the refrigerator leak. Then we can quote the actual repair.