*)*(&)&)&)&)&))&)&)*)**)*))**)*)*))*)*)**)*)*)* The Lennox unit has holes right under the blower motor. The belt had substantially worn into the pulley more than when we presented an estimate for the belts. Had to turn gas off. Will forward info. ******. This ticket should include just belt changes. Blower was not cleaned due to heat exchanger replacement repair estimate to move forward. *)*)*)***)*)*)*)*)***)*)*)*)*)*)**))*)*)*))*)*)*)*))* Today (11/17/25) the worn belts were replaced in the Carrier (s/n ending 4005) and the Lennox (s/n ending 10390). The belts were installed and tensioned. The N.W. Lennox unit (s/n ending 10390) was presenting a dirty exhaust pipe today. When the blower wheel assembly was removed the heat exchanger was inspected and there were several small holes that have appeared. The gas was turned off to the unit to ensure safety and information was gathered for a repair estimate. The blower wheel assembly was reinstalled. Thank you, Jon Q