Job Checkin

7-14-25 Apartment 207 No AC only blower Found a small amount of ice buildup on the evaporator. BLower motor was running slow, checked the Run capacitor, capacitor was bad. Install new blower run capacitor (5 MFD) Blower motor is running at this time on high speed. Currently the room temperature is 84° and the humidity id 65% My evaporator is split is about 10° Spoke to the residence it’s gonna take some time for the temperature to come down and get as we get through the humidity. I’m coming back tomorrow to do some other work another unit so I will recheck this one.