6850 West 47th Tr
Mission, KS 66203
(913) 268-6822

Job Locations
for shawnee, ks


Map of Shawnee KS
Steve R.

Steve R.


Job Checkin

7-15-25 Apartments 408 AC not cooling Found the compressor high-pressure safety tripped reset the safety system came on. I did find the condenser fan motor and run capacitor was very hot to the touch. I installed a new 5MFD run capacitor. Tyler was here on another call. He had the air compressor so we blew out the condenser coil. Also it didn’t look bad but since he had compressor here, we blow it out. The system is working at this time Apartment 207 I did a follow up check, Yesterday I replaced the run capacitor on the blower motor. I was only getting a 8-10° split Today I found the evaporator had a good build up ice on it. Removed the ice. Found the system low on refrigerant. We added 1 pound R410a . Got a pretty heavy load on it right now being 84° in the space. Apartment 203 (Pat’s) Did a follow up on the system. This is the one that kept tripping the high pressure safety. System is working at this time. The plan was replaced the high-pressure safety switch with the unit still ke