Jesse J.

Jesse J.


Job Checkin

Tech preformed CMA FULL SERVICE on 20 split systems and 8 mini split systems. System #7 ( dining room) is down due to leaking evaporator coil and being void of refrigerant. Tech recommends replacing system. System #13 is operating at this time but Air Handler has a cracked primary drain pan causing condensation from coil to leak into cabinet. Labor of replacing drain pan is extensive because evaporator coil must be removed from unit. Tech recommends replacing unit. All other systems are operating at this time but some systems require some minor repairs. Tech has attached estimates to invoice for needed repairs. Tech has also attached system performance reports along with pictures to invoice. During service of Air handlers tech did notice that majority of the units had excessive condensation on cabinets and ductwork. Tech believes challenge is due to the attic being sealed with spray foam insulation with little to no ventilation causing a humidity issue. Tech recommends possible dehumid