Tech found ah was operating but not cooling tech found the condenser motor was not operating or compressor unit was receiving 24vs and had 210 volts but compressor was not operating tech checked pressure standing pressure is 139/138 enough to engage tech believes since outdoor fan not operating made compressor go into thermal overload 1/3hp 1075rpm motor would need to be replaced to further diagnose unit