Upon arrival tech found upstairs system blowing out room temp air. System came on with no challenges, refrigerant pressures were within spec. Tech found heat strips coming on during cool mode, W1 wire was touching in t stat plate. Tech moved W1 wire, system is cooling properly at this time. No charge per customer satisfaction, thermostat was just installed today.