2330 Indian Springs Rd
Dudley, NC 28333
(919) 734-9611

Our Top Cities


Job Locations
for knightdale, nc


Map of Knightdale NC
Romario  T.

Romario T.


Job Checkin

Tech waited for the costumer to unlock the mechanical room to perform diagnostics. Found the system operating with no delta T, only room temperature air. Compressor was not running due to a failed 70uf dual run capacitor. Replaced the dual run capacitor and compressor started up without challenges. Tech noticed the refrigerant levels slightly low, tech added 1lb of R410a to aquired proper refrigerant Levels for cooling. Due to the location of the condenser(enclosed brick wall by the dryer vent exhaust) and heat load in the laundry area, slightly high head pressures will be expected, condenser coil is clean. Delta T of 20 degrees was aquired after the repairs. Tech informed Tara of the findings and repairs and approved. System is back cooling.