Tech preformed CMA FULL SERVICE on two split systems. Upon inspection of Suite A, tech found fan capacitor weak. Capacitor is rated for 5 mfd, but tested outside of operating range at 3.9 mfd. Recommend replacing. Tech spoke with Ino over the phone and was given permission to replace. Suite A unit is operating correctly after repair. Suite B is operating correct at this time. Tech added two unions to air handlers to clean drain lines.