Diagnosed no heat issue on aging boiler system with four zone valves. Found thermostats calling for heat with zone valves opening but failing to activate end switches due to faulty wiring connections. Corrected the issue by rewiring all zone valves, verified proper operation of each zone valve and confirmed all zones successfully activate the boiler. System now functioning normally. Recommended backflow preventer installation.