Mike A.

Mike A. Job Checkin

Responded to call for RS12-4 condensing boiler (LP, 4 years old) displaying overheating code and shutting down after only 10 seconds of operation. Inspection revealed blocked combustion air intake with debris and a bumblebee obstructing proper airflow. Preliminary diagnosis indicates possible scaling on heat exchanger per manufacturer's technical information. Unit was powered off for safety as heat exchanger temperature was excessively high. Return visit scheduled to perform full diagnosis with manufacturer technical support and determine if descaling procedure is required to restore proper operation.

Responded to call for RS12-4 condensing boiler (LP, 4 years old) displaying overheating code and shutting down after only 10 seconds of operation. Inspection revealed blocked combustion air intake with debris and a bumblebee obstructing proper airflow. Preliminary diagnosis indicates possible scaling on heat exchanger per manufacturer's technical information. Unit was powered off for safety as heat exchanger temperature was excessively high. Return visit scheduled to perform full diagnosis with manufacturer technical support and determine if descaling procedure is required to restore proper operation. Responded to call for RS12-4 condensing boiler (LP, 4 years old) displaying overheating code and shutting down after only 10 seconds of operation. Inspection revealed blocked combustion air intake with debris and a bumblebee obstructing proper airflow. Preliminary diagnosis indicates possible scaling on heat exchanger per manufacturer's technical information. Unit was powered off for safety as heat exchanger temperature was excessively high. Return visit scheduled to perform full diagnosis with manufacturer technical support and determine if descaling procedure is required to restore proper operation.

Ben W.

Ben W. Job Checkin

Diagnosed and repaired no heat condition on recently installed furnace. Found two issues: improperly pitched exhaust piping was corrected by cutting and re-gluing with proper slope back to unit, and cleared blockage in condensate drain system that had caused inducer motor to fill with water. Restored proper drainage and verified normal heating operation after repairs.

Diagnosed and repaired no heat condition on recently installed furnace. Found two issues: improperly pitched exhaust piping was corrected by cutting and re-gluing with proper slope back to unit, and cleared blockage in condensate drain system that had caused inducer motor to fill with water. Restored proper drainage and verified normal heating operation after repairs. Diagnosed and repaired no heat condition on recently installed furnace. Found two issues: improperly pitched exhaust piping was corrected by cutting and re-gluing with proper slope back to unit, and cleared blockage in condensate drain system that had caused inducer motor to fill with water. Restored proper drainage and verified normal heating operation after repairs.

Ben W.

Ben W. Job Checkin

Responded to a no-heat call for an 80's era furnace blowing cold air. Upon arrival, system was locked out due to overheating with supply air temperatures approaching 150°. Diagnosed severely restricted airflow with almost 1" WC static pressure on return side and minimal static on supply side. Found only two functional returns throughout home, multiple closed vents, and heavy dust accumulation in ductwork. Reset system, opened basement vents, verified all supplies were open, and inspected burners (found crusty). Noted system using cooling wire on blower for heating due to furnace running hot. Verified proper gas pressure, correct orifice, and functioning blower capacitor.

Responded to a no-heat call for an 80's era furnace blowing cold air. Upon arrival, system was locked out due to overheating with supply air temperatures approaching 150°. Diagnosed severely restricted airflow with almost 1" WC static pressure on return side and minimal static on supply side. Found only two functional returns throughout home, multiple closed vents, and heavy dust accumulation in ductwork. Reset system, opened basement vents, verified all supplies were open, and inspected burners (found crusty). Noted system using cooling wire on blower for heating due to furnace running hot. Verified proper gas pressure, correct orifice, and functioning blower capacitor. Responded to a no-heat call for an 80's era furnace blowing cold air. Upon arrival, system was locked out due to overheating with supply air temperatures approaching 150°. Diagnosed severely restricted airflow with almost 1" WC static pressure on return side and minimal static on supply side. Found only two functional returns throughout home, multiple closed vents, and heavy dust accumulation in ductwork. Reset system, opened basement vents, verified all supplies were open, and inspected burners (found crusty). Noted system using cooling wire on blower for heating due to furnace running hot. Verified proper gas pressure, correct orifice, and functioning blower capacitor.

Ben W.

Ben W. Job Checkin

Performed standard oil furnace tune-up including nozzle replacement and filter change. Inspected capacitor and found it in working condition. Identified and addressed oil leak at filter housing by replacing filter and gaskets, with no residual leakage observed after repair. Advised customer that oil tank gauge readings appear inaccurate, though customer is aware of current oil levels.

Performed standard oil furnace tune-up including nozzle replacement and filter change. Inspected capacitor and found it in working condition. Identified and addressed oil leak at filter housing by replacing filter and gaskets, with no residual leakage observed after repair. Advised customer that oil tank gauge readings appear inaccurate, though customer is aware of current oil levels. Performed standard oil furnace tune-up including nozzle replacement and filter change. Inspected capacitor and found it in working condition. Identified and addressed oil leak at filter housing by replacing filter and gaskets, with no residual leakage observed after repair. Advised customer that oil tank gauge readings appear inaccurate, though customer is aware of current oil levels.

Roger M.

Roger M. Job Checkin

Completed annual furnace tune-up on 9-year-old system as part of 2x yearly recurring service agreement. Performed comprehensive inspection of heating components including examination of evaporator coil condition and electrical connections. All systems functioning properly with no issues identified.

Completed annual furnace tune-up on 9-year-old system as part of 2x yearly recurring service agreement. Performed comprehensive inspection of heating components including examination of evaporator coil condition and electrical connections. All systems functioning properly with no issues identified. Completed annual furnace tune-up on 9-year-old system as part of 2x yearly recurring service agreement. Performed comprehensive inspection of heating components including examination of evaporator coil condition and electrical connections. All systems functioning properly with no issues identified.

Dan S.

Dan S. Job Checkin

Diagnosed heating system failure in white boiler with no flow to house. Identified multiple issues including a stuck floor control valve, faulty pressure gauge, and possibly malfunctioning ball valve near circulator pump. Replaced pressure/temperature gauge, freed up control valve to restore water flow, and installed relief valve. System was properly pressurized and bled out; however, circulation issues persisted despite pump appearing operational. Recommended expansion tank replacement and auto fill system upgrade from filter trial to conventional configuration. Scheduled follow-up service with boiler specialist for further diagnosis.

Diagnosed heating system failure in white boiler with no flow to house. Identified multiple issues including a stuck floor control valve, faulty pressure gauge, and possibly malfunctioning ball valve near circulator pump. Replaced pressure/temperature gauge, freed up control valve to restore water flow, and installed relief valve. System was properly pressurized and bled out; however, circulation issues persisted despite pump appearing operational. Recommended expansion tank replacement and auto fill system upgrade from filter trial to conventional configuration. Scheduled follow-up service with boiler specialist for further diagnosis. Diagnosed heating system failure in white boiler with no flow to house. Identified multiple issues including a stuck floor control valve, faulty pressure gauge, and possibly malfunctioning ball valve near circulator pump. Replaced pressure/temperature gauge, freed up control valve to restore water flow, and installed relief valve. System was properly pressurized and bled out; however, circulation issues persisted despite pump appearing operational. Recommended expansion tank replacement and auto fill system upgrade from filter trial to conventional configuration. Scheduled follow-up service with boiler specialist for further diagnosis.

Dan S.

Dan S. Job Checkin

Responded to a return service call to install a relief valve on customer's boiler system. Successfully installed the relief valve and performed a complete system bleed, but noted the boiler was still overheating due to poor water circulation. Inspection revealed the circulator pump was operational but ineffective, with a potentially defective ball valve above the pump that may have a broken shaft preventing proper opening/closing. Recommended further diagnosis by a boiler specialist.

Responded to a return service call to install a relief valve on customer's boiler system. Successfully installed the relief valve and performed a complete system bleed, but noted the boiler was still overheating due to poor water circulation. Inspection revealed the circulator pump was operational but ineffective, with a potentially defective ball valve above the pump that may have a broken shaft preventing proper opening/closing. Recommended further diagnosis by a boiler specialist. Responded to a return service call to install a relief valve on customer's boiler system. Successfully installed the relief valve and performed a complete system bleed, but noted the boiler was still overheating due to poor water circulation. Inspection revealed the circulator pump was operational but ineffective, with a potentially defective ball valve above the pump that may have a broken shaft preventing proper opening/closing. Recommended further diagnosis by a boiler specialist.

Logan P.

Logan P. Job Checkin

Responded to service call for a leaking piercing valve on a 3/8" hot water line that was failing to shut off after HVAC contractor removed an old humidifier. Removed the defective piercing valve and repaired the damaged section of copper piping using a SharkBite coupling to restore proper system operation.

Responded to service call for a leaking piercing valve on a 3/8" hot water line that was failing to shut off after HVAC contractor removed an old humidifier. Removed the defective piercing valve and repaired the damaged section of copper piping using a SharkBite coupling to restore proper system operation.

Trent L.

Trent L. Job Checkin

Diagnosed 20-year-old boiler system not producing heat due to overheating from insufficient water circulation and a leaking relief valve. Opted against adding water to the hot cast iron boiler to prevent damage. Ordered new relief valve and recommended system bleeding to restore proper circulation, with contingency plan for possible circulator pump replacement if needed.

Diagnosed 20-year-old boiler system not producing heat due to overheating from insufficient water circulation and a leaking relief valve. Opted against adding water to the hot cast iron boiler to prevent damage. Ordered new relief valve and recommended system bleeding to restore proper circulation, with contingency plan for possible circulator pump replacement if needed. Diagnosed 20-year-old boiler system not producing heat due to overheating from insufficient water circulation and a leaking relief valve. Opted against adding water to the hot cast iron boiler to prevent damage. Ordered new relief valve and recommended system bleeding to restore proper circulation, with contingency plan for possible circulator pump replacement if needed.

Gary L.

Gary L. Job Checkin

Diagnosed 22-year-old York furnace with no heat issue. Found inducer draft motor seized, running hot, and collector box cracked. Recommended replacement of both draft inducer motor and collector box due to age and condition of unit.

Diagnosed 22-year-old York furnace with no heat issue. Found inducer draft motor seized, running hot, and collector box cracked. Recommended replacement of both draft inducer motor and collector box due to age and condition of unit. Diagnosed 22-year-old York furnace with no heat issue. Found inducer draft motor seized, running hot, and collector box cracked. Recommended replacement of both draft inducer motor and collector box due to age and condition of unit.

Mike A.

Mike A. Job Checkin

Performed furnace burner assembly replacement. Installed new burners after identifying corrosion and rust on the existing assembly. Completed comprehensive verification of inlet gas pressure and both stages, checked terminations, and conducted performance testing to ensure proper burner operation.

Performed furnace burner assembly replacement. Installed new burners after identifying corrosion and rust on the existing assembly. Completed comprehensive verification of inlet gas pressure and both stages, checked terminations, and conducted performance testing to ensure proper burner operation. Performed furnace burner assembly replacement. Installed new burners after identifying corrosion and rust on the existing assembly. Completed comprehensive verification of inlet gas pressure and both stages, checked terminations, and conducted performance testing to ensure proper burner operation.

Beca R.

Beca R. Job Checkin

Diagnosed furnace no-heat issue caused by malfunctioning burners. Performed temporary cleaning and manually assisted ignition to restore heating function. Ordered replacement burner assembly as existing components were not reliably self-igniting.

Diagnosed furnace no-heat issue caused by malfunctioning burners. Performed temporary cleaning and manually assisted ignition to restore heating function. Ordered replacement burner assembly as existing components were not reliably self-igniting.

Beca R.

Beca R. Job Checkin

Performed annual furnace tune-up on 10-year-old FRP unit. Conducted comprehensive maintenance including flame sensor cleaning, electrical component testing, filter replacement, and condensate hose verification. Visual inspection of heat exchanger showed no issues. All systems functioning within manufacturer specifications.

Performed annual furnace tune-up on 10-year-old FRP unit. Conducted comprehensive maintenance including flame sensor cleaning, electrical component testing, filter replacement, and condensate hose verification. Visual inspection of heat exchanger showed no issues. All systems functioning within manufacturer specifications. Performed annual furnace tune-up on 10-year-old FRP unit. Conducted comprehensive maintenance including flame sensor cleaning, electrical component testing, filter replacement, and condensate hose verification. Visual inspection of heat exchanger showed no issues. All systems functioning within manufacturer specifications.

Beca R.

Beca R. Job Checkin

Completed biannual furnace tune-up maintenance on two Amana heating units. Services performed include cleaning flame sensor, electrical testing, verification of clear drain lines, and combustion analysis (measured readings: CO 25P, CO2 9.0%, XAIR 52.8%). All systems functioning properly with parameters within specifications. Customer's filter was recently replaced and still in good condition.

Completed biannual furnace tune-up maintenance on two Amana heating units. Services performed include cleaning flame sensor, electrical testing, verification of clear drain lines, and combustion analysis (measured readings: CO 25P, CO2 9.0%, XAIR 52.8%). All systems functioning properly with parameters within specifications. Customer's filter was recently replaced and still in good condition. Completed biannual furnace tune-up maintenance on two Amana heating units. Services performed include cleaning flame sensor, electrical testing, verification of clear drain lines, and combustion analysis (measured readings: CO 25P, CO2 9.0%, XAIR 52.8%). All systems functioning properly with parameters within specifications. Customer's filter was recently replaced and still in good condition.

Beca R.

Beca R. Job Checkin

Performed scheduled bi-annual furnace maintenance on two Amana units. Services included cleaning flame sensor, testing electrical components, verifying clear drain lines, and conducting combustion analysis (CO 25P, CO2 9.0%, XAIR 52.8%) - all readings within specifications. Filter was relatively new and did not require replacement. Both furnaces are operating properly with no issues detected.

Performed scheduled bi-annual furnace maintenance on two Amana units. Services included cleaning flame sensor, testing electrical components, verifying clear drain lines, and conducting combustion analysis (CO 25P, CO2 9.0%, XAIR 52.8%) - all readings within specifications. Filter was relatively new and did not require replacement. Both furnaces are operating properly with no issues detected. Performed scheduled bi-annual furnace maintenance on two Amana units. Services included cleaning flame sensor, testing electrical components, verifying clear drain lines, and conducting combustion analysis (CO 25P, CO2 9.0%, XAIR 52.8%) - all readings within specifications. Filter was relatively new and did not require replacement. Both furnaces are operating properly with no issues detected.