Gary L.

Gary L. Job Checkin

Responded to no heat complaint on 5-year-old Goodman furnace. Diagnostic inspection revealed furnace attempting to ignite (clicking) but failing to maintain flame. Identified corroded flame sensor and signs of rust in cabinet, though no active leaks were present. Successfully replaced flame sensor, restoring normal heating function.

Responded to no heat complaint on 5-year-old Goodman furnace. Diagnostic inspection revealed furnace attempting to ignite (clicking) but failing to maintain flame. Identified corroded flame sensor and signs of rust in cabinet, though no active leaks were present. Successfully replaced flame sensor, restoring normal heating function. Responded to no heat complaint on 5-year-old Goodman furnace. Diagnostic inspection revealed furnace attempting to ignite (clicking) but failing to maintain flame. Identified corroded flame sensor and signs of rust in cabinet, though no active leaks were present. Successfully replaced flame sensor, restoring normal heating function.

Koshoua V.

Koshoua V. Job Checkin

Responded to service call regarding "needs maintenance" alert displayed on Bryant thermostat following routine maintenance performed in August. Verified system was operating correctly with no active faults. Explained to homeowner that the notification was a standard reminder for scheduled maintenance rather than an operational issue. Reset maintenance reminder on thermostat.

Responded to service call regarding "needs maintenance" alert displayed on Bryant thermostat following routine maintenance performed in August. Verified system was operating correctly with no active faults. Explained to homeowner that the notification was a standard reminder for scheduled maintenance rather than an operational issue. Reset maintenance reminder on thermostat.

Koshoua V.

Koshoua V. Job Checkin

Performed comprehensive furnace tune-up service including correction of gas train pressure from 3.671 inWC to 3.30 inWC and clearing of condensate drain line and trap that contained accumulated spiderwebbing and debris. Verified proper operation of all critical components (inducer motor, capacitor, pressure switch, control board connections, and thermostat), confirmed moderate condition of return air filter, and documented combustion CO at 18 ppm, with furnace now operating normally with no immediate concerns.

Performed comprehensive furnace tune-up service including correction of gas train pressure from 3.671 inWC to 3.30 inWC and clearing of condensate drain line and trap that contained accumulated spiderwebbing and debris. Verified proper operation of all critical components (inducer motor, capacitor, pressure switch, control board connections, and thermostat), confirmed moderate condition of return air filter, and documented combustion CO at 18 ppm, with furnace now operating normally with no immediate concerns. Performed comprehensive furnace tune-up service including correction of gas train pressure from 3.671 inWC to 3.30 inWC and clearing of condensate drain line and trap that contained accumulated spiderwebbing and debris. Verified proper operation of all critical components (inducer motor, capacitor, pressure switch, control board connections, and thermostat), confirmed moderate condition of return air filter, and documented combustion CO at 18 ppm, with furnace now operating normally with no immediate concerns.

Koshoua V.

Koshoua V. Job Checkin

Responded to no heat complaint for 25+ year old furnace that was cycling without ignition. Bypassed furnace control board temporarily to restore heating function. Upon removing bypass clippers, unit continued to operate normally. Performed comprehensive diagnostics including gas pressure verification, carbon monoxide testing, and heat exchanger inspection with no hazardous conditions found. Cleaned flame sensor and checked pressure switch and flame rollout switches. Discovered extremely dirty furnace filter clogged with pet fur and dirt causing airflow restriction. Educated homeowner on proper filter maintenance, condensation trap cleaning, and keeping furnace area clear of obstructions. Unit now functioning properly.

Responded to no heat complaint for 25+ year old furnace that was cycling without ignition. Bypassed furnace control board temporarily to restore heating function. Upon removing bypass clippers, unit continued to operate normally. Performed comprehensive diagnostics including gas pressure verification, carbon monoxide testing, and heat exchanger inspection with no hazardous conditions found. Cleaned flame sensor and checked pressure switch and flame rollout switches. Discovered extremely dirty furnace filter clogged with pet fur and dirt causing airflow restriction. Educated homeowner on proper filter maintenance, condensation trap cleaning, and keeping furnace area clear of obstructions. Unit now functioning properly. Responded to no heat complaint for 25+ year old furnace that was cycling without ignition. Bypassed furnace control board temporarily to restore heating function. Upon removing bypass clippers, unit continued to operate normally. Performed comprehensive diagnostics including gas pressure verification, carbon monoxide testing, and heat exchanger inspection with no hazardous conditions found. Cleaned flame sensor and checked pressure switch and flame rollout switches. Discovered extremely dirty furnace filter clogged with pet fur and dirt causing airflow restriction. Educated homeowner on proper filter maintenance, condensation trap cleaning, and keeping furnace area clear of obstructions. Unit now functioning properly.

Colten C.

Colten C. Job Checkin

Responded to no heat call for 3-year-old LP furnace. Diagnosed low pressure switch stuck in closed position. Replaced faulty pressure switch, verified complete system operation was restored, and confirmed all other components were functioning properly.

Responded to no heat call for 3-year-old LP furnace. Diagnosed low pressure switch stuck in closed position. Replaced faulty pressure switch, verified complete system operation was restored, and confirmed all other components were functioning properly. Responded to no heat call for 3-year-old LP furnace. Diagnosed low pressure switch stuck in closed position. Replaced faulty pressure switch, verified complete system operation was restored, and confirmed all other components were functioning properly.

Craig M.

Craig M. Job Checkin

Performed annual maintenance on gas furnace, confirming system is operational with no issues identified. Inspected control board and electrical connections to ensure proper function. Additionally, secured and capped off gas line as requested by customer.

Performed annual maintenance on gas furnace, confirming system is operational with no issues identified. Inspected control board and electrical connections to ensure proper function. Additionally, secured and capped off gas line as requested by customer. Performed annual maintenance on gas furnace, confirming system is operational with no issues identified. Inspected control board and electrical connections to ensure proper function. Additionally, secured and capped off gas line as requested by customer.

Kegan M.

Kegan M. Job Checkin

Performed comprehensive inspection of 20-year-old Rheem Performance water heater and associated plumbing system. Evaluated three outdoor spigots requiring replacement. Documented current installation conditions including supply lines, drainage configuration, and connection points. Provided customer with detailed replacement options and repair estimates for multiple plumbing projects as requested.

Performed comprehensive inspection of 20-year-old Rheem Performance water heater and associated plumbing system. Evaluated three outdoor spigots requiring replacement. Documented current installation conditions including supply lines, drainage configuration, and connection points. Provided customer with detailed replacement options and repair estimates for multiple plumbing projects as requested. Performed comprehensive inspection of 20-year-old Rheem Performance water heater and associated plumbing system. Evaluated three outdoor spigots requiring replacement. Documented current installation conditions including supply lines, drainage configuration, and connection points. Provided customer with detailed replacement options and repair estimates for multiple plumbing projects as requested.

Bryson E.

Bryson E. Job Checkin

Diagnosed and resolved low hot water pressure at kitchen faucet caused by sediment accumulation in the plumbing lines. Installed whole-house sediment filter to address ongoing water quality issues from the customer's well water system, effectively restoring proper flow to both hot and cold water sides of the kitchen faucet.

Diagnosed and resolved low hot water pressure at kitchen faucet caused by sediment accumulation in the plumbing lines. Installed whole-house sediment filter to address ongoing water quality issues from the customer's well water system, effectively restoring proper flow to both hot and cold water sides of the kitchen faucet. Diagnosed and resolved low hot water pressure at kitchen faucet caused by sediment accumulation in the plumbing lines. Installed whole-house sediment filter to address ongoing water quality issues from the customer's well water system, effectively restoring proper flow to both hot and cold water sides of the kitchen faucet.

Bryson E.

Bryson E. Job Checkin

Responded to emergency water leak in basement ceiling where a half-inch copper hot water line had failed. Shut off water supply to prevent further damage, then replaced damaged section of copper pipe with PEX tubing. Reestablished water service, fired up water heater, and replaced toilet angle stop to restore full functionality to the residence's plumbing system.

Responded to emergency water leak in basement ceiling where a half-inch copper hot water line had failed. Shut off water supply to prevent further damage, then replaced damaged section of copper pipe with PEX tubing. Reestablished water service, fired up water heater, and replaced toilet angle stop to restore full functionality to the residence's plumbing system. Responded to emergency water leak in basement ceiling where a half-inch copper hot water line had failed. Shut off water supply to prevent further damage, then replaced damaged section of copper pipe with PEX tubing. Reestablished water service, fired up water heater, and replaced toilet angle stop to restore full functionality to the residence's plumbing system.

Trent L.

Trent L. Job Checkin

Completed warranty service on Honeywell standby generator by replacing the manual shut off switch. After installation, reset the system and performed operational testing to verify proper functionality. All systems are now operating as specified by manufacturer standards.

Completed warranty service on Honeywell standby generator by replacing the manual shut off switch. After installation, reset the system and performed operational testing to verify proper functionality. All systems are now operating as specified by manufacturer standards.

Craig M.

Craig M. Job Checkin

Performed annual tune-up maintenance on customer's 1-year-old natural gas furnace. Inspected heat exchanger and exhaust components, verified proper system operation. No issues found; system operating within normal parameters. Recommended continuing regular maintenance schedule to maintain efficiency and extend equipment life.

Performed annual tune-up maintenance on customer's 1-year-old natural gas furnace. Inspected heat exchanger and exhaust components, verified proper system operation. No issues found; system operating within normal parameters. Recommended continuing regular maintenance schedule to maintain efficiency and extend equipment life. Performed annual tune-up maintenance on customer's 1-year-old natural gas furnace. Inspected heat exchanger and exhaust components, verified proper system operation. No issues found; system operating within normal parameters. Recommended continuing regular maintenance schedule to maintain efficiency and extend equipment life.

Bryson E.

Bryson E. Job Checkin

Responded to service call for kitchen sink backup. Investigation revealed drainage issues when sink and dishwasher were in use, despite clear P-trap. Successfully restored proper drainage function by augering the kitchen sink line, clearing blockage located beyond the trap assembly.

Responded to service call for kitchen sink backup. Investigation revealed drainage issues when sink and dishwasher were in use, despite clear P-trap. Successfully restored proper drainage function by augering the kitchen sink line, clearing blockage located beyond the trap assembly. Responded to service call for kitchen sink backup. Investigation revealed drainage issues when sink and dishwasher were in use, despite clear P-trap. Successfully restored proper drainage function by augering the kitchen sink line, clearing blockage located beyond the trap assembly.

Moe R.

Moe R. Job Checkin

Completed previously sold repair on 16-year-old Lennox HVAC system, replacing the dual capacitor at the outdoor heat pump unit and the flame sensor in the furnace. All components were tested and verified to be operating correctly after installation of the FLAME SENSOR and DUAL VALUE SECONDARY START DEVICE.

Completed previously sold repair on 16-year-old Lennox HVAC system, replacing the dual capacitor at the outdoor heat pump unit and the flame sensor in the furnace. All components were tested and verified to be operating correctly after installation of the FLAME SENSOR and DUAL VALUE SECONDARY START DEVICE. Completed previously sold repair on 16-year-old Lennox HVAC system, replacing the dual capacitor at the outdoor heat pump unit and the flame sensor in the furnace. All components were tested and verified to be operating correctly after installation of the FLAME SENSOR and DUAL VALUE SECONDARY START DEVICE.

David B.

David B. Job Checkin

AC Repair: Diagnosed and replaced a swollen run capacitor that had caused an AC unit to fail during startup. Ensured proper voltage readings and tested full-cycle cooling operation, restoring reliable functionality to the system.


Matt N.

Matt N. Job Checkin

Air Conditioning System Repairs: Replaced a malfunctioning start capacitor that was preventing the compressor from engaging during startup. The new capacitor was installed with surge protection, and the system was thoroughly tested to confirm reliable, efficient operation under normal and high-load conditions.