Kegan M.

Kegan M. Job Checkin

Diagnosed tank water heater displaying 3 green lights with no hot water output. Inspection revealed failed blower motor assembly as the root cause. Provided customer with replacement options for a new water heater system.

Diagnosed tank water heater displaying 3 green lights with no hot water output. Inspection revealed failed blower motor assembly as the root cause. Provided customer with replacement options for a new water heater system.

Mike B.

Mike B. Job Checkin

Installed stamped steel return air grill with damper for upstairs air handler to improve circulation in area experiencing overheating issues. Verified proper installation of filter box (20x20x1) with appropriate ductwork connections to enhance airflow distribution.

Installed stamped steel return air grill with damper for upstairs air handler to improve circulation in area experiencing overheating issues. Verified proper installation of filter box (20x20x1) with appropriate ductwork connections to enhance airflow distribution.

Mike B.

Mike B. Job Checkin

Responded to a no-heat service call for an older boiler system. Upon inspection, discovered a condensate cup that wasn't properly tightened, causing ongoing leakage since installation. Tightened the component to stop the active leak, cleaned the affected floor area, and noted some black organic growth on the back wall which customer acknowledged. Advised customer to periodically check the area for any future leakage issues.

Responded to a no-heat service call for an older boiler system. Upon inspection, discovered a condensate cup that wasn't properly tightened, causing ongoing leakage since installation. Tightened the component to stop the active leak, cleaned the affected floor area, and noted some black organic growth on the back wall which customer acknowledged. Advised customer to periodically check the area for any future leakage issues. Responded to a no-heat service call for an older boiler system. Upon inspection, discovered a condensate cup that wasn't properly tightened, causing ongoing leakage since installation. Tightened the component to stop the active leak, cleaned the affected floor area, and noted some black organic growth on the back wall which customer acknowledged. Advised customer to periodically check the area for any future leakage issues.

Kegan M.

Kegan M. Job Checkin

Responded to emergency water leak caused by broken shower handle. Inspected the Moen shower valve assembly and identified a failed cartridge as the source of the leak. Successfully replaced the defective Moen cartridge, restored proper functionality to the shower control, and verified complete resolution of the leak. Water service to home was restored after repair verification.

Responded to emergency water leak caused by broken shower handle. Inspected the Moen shower valve assembly and identified a failed cartridge as the source of the leak. Successfully replaced the defective Moen cartridge, restored proper functionality to the shower control, and verified complete resolution of the leak. Water service to home was restored after repair verification.

Mike B.

Mike B. Job Checkin

Responded to no-heat call on 3-year old HVAC system. Customer reported circulation motor issues with diagnostic flash codes 1+2. Upon inspection, determined that customer was not allowing for the system's required 90-second purge cycle before fan operation. Demonstrated proper operation to customer, verified multiple successful heating cycles, and confirmed system is functioning as designed with no repairs needed.

Responded to no-heat call on 3-year old HVAC system. Customer reported circulation motor issues with diagnostic flash codes 1+2. Upon inspection, determined that customer was not allowing for the system's required 90-second purge cycle before fan operation. Demonstrated proper operation to customer, verified multiple successful heating cycles, and confirmed system is functioning as designed with no repairs needed. Responded to no-heat call on 3-year old HVAC system. Customer reported circulation motor issues with diagnostic flash codes 1+2. Upon inspection, determined that customer was not allowing for the system's required 90-second purge cycle before fan operation. Demonstrated proper operation to customer, verified multiple successful heating cycles, and confirmed system is functioning as designed with no repairs needed.

Mike B.

Mike B. Job Checkin

Performed routine maintenance on a 4-5 year old LP furnace in mobile home. Conducted comprehensive inspection including heat exchanger evaluation, operational testing of all components, and standard tune-up procedures. All systems functioning properly with no defects or issues identified.

Performed routine maintenance on a 4-5 year old LP furnace in mobile home. Conducted comprehensive inspection including heat exchanger evaluation, operational testing of all components, and standard tune-up procedures. All systems functioning properly with no defects or issues identified. Performed routine maintenance on a 4-5 year old LP furnace in mobile home. Conducted comprehensive inspection including heat exchanger evaluation, operational testing of all components, and standard tune-up procedures. All systems functioning properly with no defects or issues identified.

Shawn G.

Shawn G. Job Checkin

Responded to emergency service call for a broken pipe in garage causing water leakage. Diagnosed cracked ball valve that had failed due to freezing conditions. Successfully replaced damaged ball valve and adjacent pipe section, restoring proper water flow and preventing further leakage into the garage area. System tested and confirmed operational.

Responded to emergency service call for a broken pipe in garage causing water leakage. Diagnosed cracked ball valve that had failed due to freezing conditions. Successfully replaced damaged ball valve and adjacent pipe section, restoring proper water flow and preventing further leakage into the garage area. System tested and confirmed operational. Responded to emergency service call for a broken pipe in garage causing water leakage. Diagnosed cracked ball valve that had failed due to freezing conditions. Successfully replaced damaged ball valve and adjacent pipe section, restoring proper water flow and preventing further leakage into the garage area. System tested and confirmed operational.

Dan S.

Dan S. Job Checkin

Successfully completed a repair by replacing the combustion inducer assembly and all four main burners per approved estimate. System was test run for 30 minutes following installation to verify proper operation and performance.

Successfully completed a repair by replacing the combustion inducer assembly and all four main burners per approved estimate. System was test run for 30 minutes following installation to verify proper operation and performance. Successfully completed a repair by replacing the combustion inducer assembly and all four main burners per approved estimate. System was test run for 30 minutes following installation to verify proper operation and performance.

Mike B.

Mike B. Job Checkin

Performed fall maintenance and winter startup on geothermal system, verifying proper operation. Identified and corrected valve settings on Munchkin boiler, adding written instructions directly on the unit for client reference. Added water to the load side as needed and sold replacement register to be installed on a future visit.

Performed fall maintenance and winter startup on geothermal system, verifying proper operation. Identified and corrected valve settings on Munchkin boiler, adding written instructions directly on the unit for client reference. Added water to the load side as needed and sold replacement register to be installed on a future visit.

Dan S.

Dan S. Job Checkin

Responded to no heat complaint for 17-year-old LP system serving mixed-use building. Diagnosed tripped limit switch on inducer caused by recently installed filter after previous filter was heavily clogged. Reset limit switch, performed heat exchanger inspection, and restored heat operation. Noted significant rust on burners and concerning inducer motor noise; provided customer with replacement options for these degraded components.

Responded to no heat complaint for 17-year-old LP system serving mixed-use building. Diagnosed tripped limit switch on inducer caused by recently installed filter after previous filter was heavily clogged. Reset limit switch, performed heat exchanger inspection, and restored heat operation. Noted significant rust on burners and concerning inducer motor noise; provided customer with replacement options for these degraded components.

Mike B.

Mike B. Job Checkin

Responded to service call at customer's bunk house for a missing plug on the side of the Goodman furnace, which was likely dislodged during previous gas valve replacement service. Located and reinstalled the missing furnace plug to restore proper operation and system integrity.

Responded to service call at customer's bunk house for a missing plug on the side of the Goodman furnace, which was likely dislodged during previous gas valve replacement service. Located and reinstalled the missing furnace plug to restore proper operation and system integrity. Responded to service call at customer's bunk house for a missing plug on the side of the Goodman furnace, which was likely dislodged during previous gas valve replacement service. Located and reinstalled the missing furnace plug to restore proper operation and system integrity.

Trevor P.

Trevor P. Job Checkin

Diagnosed 32-year-old oil boiler that was not firing. Investigation revealed a wire had become disconnected from the electrode, likely from previous service interaction when nozzle work was performed. Reconnected the wire securely to the electrode and verified proper system operation. System now functioning normally.

Diagnosed 32-year-old oil boiler that was not firing. Investigation revealed a wire had become disconnected from the electrode, likely from previous service interaction when nozzle work was performed. Reconnected the wire securely to the electrode and verified proper system operation. System now functioning normally.

Mike B.

Mike B. Job Checkin

Successfully installed new Amtrol expansion tank as per approved estimate. System was refilled, air purged from lines, and proper operation verified after installation. All work completed according to specifications with residential hydronic heating system now functioning correctly.

Successfully installed new Amtrol expansion tank as per approved estimate. System was refilled, air purged from lines, and proper operation verified after installation. All work completed according to specifications with residential hydronic heating system now functioning correctly. Successfully installed new Amtrol expansion tank as per approved estimate. System was refilled, air purged from lines, and proper operation verified after installation. All work completed according to specifications with residential hydronic heating system now functioning correctly.

Doug T.

Doug T. Job Checkin

Replaced cracked PVC bushing on Rusco R500 sediment filter system which was actively leaking. Installed new filter assembly and re-piped connections to ensure proper operation and eliminate water leakage.

Replaced cracked PVC bushing on Rusco R500 sediment filter system which was actively leaking. Installed new filter assembly and re-piped connections to ensure proper operation and eliminate water leakage. Replaced cracked PVC bushing on Rusco R500 sediment filter system which was actively leaking. Installed new filter assembly and re-piped connections to ensure proper operation and eliminate water leakage.

Trent L.

Trent L. Job Checkin

Responded to service call for non-starting boiler system in gym. Discovered low system pressure and refilled system, but unit continued to overheat. After assessment, determined potential circulation pump failure preventing proper water movement through the system. Temporarily resolved overheating by adjusting valve positions to force full system circulation, which successfully restored heating to the building. Recommended follow-up visit by senior boiler technician to conduct comprehensive diagnosis and address potential pump issues.

Responded to service call for non-starting boiler system in gym. Discovered low system pressure and refilled system, but unit continued to overheat. After assessment, determined potential circulation pump failure preventing proper water movement through the system. Temporarily resolved overheating by adjusting valve positions to force full system circulation, which successfully restored heating to the building. Recommended follow-up visit by senior boiler technician to conduct comprehensive diagnosis and address potential pump issues. Responded to service call for non-starting boiler system in gym. Discovered low system pressure and refilled system, but unit continued to overheat. After assessment, determined potential circulation pump failure preventing proper water movement through the system. Temporarily resolved overheating by adjusting valve positions to force full system circulation, which successfully restored heating to the building. Recommended follow-up visit by senior boiler technician to conduct comprehensive diagnosis and address potential pump issues.