Mike B.

Mike B. Job Checkin

Diagnosed and serviced boiler that was locked out due to feed water issue caused by customer having water supply shut off. Restored proper operation by addressing feed water system and performed comprehensive service. Also inspected furnace heat exchanger and noted deteriorated burners which will require replacement.

Diagnosed and serviced boiler that was locked out due to feed water issue caused by customer having water supply shut off. Restored proper operation by addressing feed water system and performed comprehensive service. Also inspected furnace heat exchanger and noted deteriorated burners which will require replacement. Diagnosed and serviced boiler that was locked out due to feed water issue caused by customer having water supply shut off. Restored proper operation by addressing feed water system and performed comprehensive service. Also inspected furnace heat exchanger and noted deteriorated burners which will require replacement.

Noah S

Noah S Job Checkin

Performed a 2-hour repair service to address a failing Premier flush valve in toilet. Removed existing components and installed new Kohler toilet flush valve system with large diameter valve and gaskets. Completed installation and verified proper flushing operation.

Performed a 2-hour repair service to address a failing Premier flush valve in toilet. Removed existing components and installed new Kohler toilet flush valve system with large diameter valve and gaskets. Completed installation and verified proper flushing operation. Performed a 2-hour repair service to address a failing Premier flush valve in toilet. Removed existing components and installed new Kohler toilet flush valve system with large diameter valve and gaskets. Completed installation and verified proper flushing operation.

Mike B.

Mike B. Job Checkin

Found LP conversion issue on recently installed furnace (8 months old). Unit was exhibiting short cycling behavior and discovered significant soot buildup due to improper fuel configuration. After consultation with supervisor, complete furnace replacement was authorized and performed same day.

Found LP conversion issue on recently installed furnace (8 months old). Unit was exhibiting short cycling behavior and discovered significant soot buildup due to improper fuel configuration. After consultation with supervisor, complete furnace replacement was authorized and performed same day. Found LP conversion issue on recently installed furnace (8 months old). Unit was exhibiting short cycling behavior and discovered significant soot buildup due to improper fuel configuration. After consultation with supervisor, complete furnace replacement was authorized and performed same day.

Mike B.

Mike B. Job Checkin

Inspected customer's water filtration system that was previously installed by our team. Determined customer needs replacement filter for existing unit. Documented current installation with photos and submitted formal request to Parts Department to source appropriate replacement water filter.

Inspected customer's water filtration system that was previously installed by our team. Determined customer needs replacement filter for existing unit. Documented current installation with photos and submitted formal request to Parts Department to source appropriate replacement water filter.

Mike B.

Mike B. Job Checkin

Diagnosed issue with no heat complaint in aging HVAC system; determined problem was caused by faulty connection in damper assembly. During troubleshooting and wire tracing, damper began functioning properly. Monitored system operation for approximately 30 minutes to confirm proper heating throughout the residence, verifying radiator function on both floors. Although temporarily operational, submitted request for replacement damper assembly due to intermittent nature of the connection issue.

Diagnosed issue with no heat complaint in aging HVAC system; determined problem was caused by faulty connection in damper assembly. During troubleshooting and wire tracing, damper began functioning properly. Monitored system operation for approximately 30 minutes to confirm proper heating throughout the residence, verifying radiator function on both floors. Although temporarily operational, submitted request for replacement damper assembly due to intermittent nature of the connection issue. Diagnosed issue with no heat complaint in aging HVAC system; determined problem was caused by faulty connection in damper assembly. During troubleshooting and wire tracing, damper began functioning properly. Monitored system operation for approximately 30 minutes to confirm proper heating throughout the residence, verifying radiator function on both floors. Although temporarily operational, submitted request for replacement damper assembly due to intermittent nature of the connection issue.

Noah S

Noah S Job Checkin

Performed comprehensive plumbing inspection and service on two running toilets. Replaced customer-supplied flush valve in one toilet showing mineral buildup in tank. Serviced whole house filter system and documented condition of RO filtration system. Submitted parts order form for Kohler toilet replacement components.

Performed comprehensive plumbing inspection and service on two running toilets. Replaced customer-supplied flush valve in one toilet showing mineral buildup in tank. Serviced whole house filter system and documented condition of RO filtration system. Submitted parts order form for Kohler toilet replacement components. Performed comprehensive plumbing inspection and service on two running toilets. Replaced customer-supplied flush valve in one toilet showing mineral buildup in tank. Serviced whole house filter system and documented condition of RO filtration system. Submitted parts order form for Kohler toilet replacement components.

Mike B.

Mike B. Job Checkin

Inspected leaking valve at bottom of customer's fuel oil tank that was previously identified during tune-up service last month. Observed increased dripping since tank was recently filled. Tightened valve nut and cleaned oil residue. Informed customer that complete valve replacement would require emptying the tank first, as the valve is approximately 60 years old.

Inspected leaking valve at bottom of customer's fuel oil tank that was previously identified during tune-up service last month. Observed increased dripping since tank was recently filled. Tightened valve nut and cleaned oil residue. Informed customer that complete valve replacement would require emptying the tank first, as the valve is approximately 60 years old. Inspected leaking valve at bottom of customer's fuel oil tank that was previously identified during tune-up service last month. Observed increased dripping since tank was recently filled. Tightened valve nut and cleaned oil residue. Informed customer that complete valve replacement would require emptying the tank first, as the valve is approximately 60 years old.

Mike B.

Mike B. Job Checkin

Responded to no-heat complaint on 12-year-old Lennox furnace. Diagnostic revealed error codes HA478 and E126, with circuit board failure evident upon inspection. Further examination identified potential perforations in the heat exchanger with visible rust staining along seams. Documented defective components with photos. Furnace requires both control board replacement and heat exchanger evaluation. Customer advised of repair options and replacement recommendation due to equipment age and condition.

Responded to no-heat complaint on 12-year-old Lennox furnace. Diagnostic revealed error codes HA478 and E126, with circuit board failure evident upon inspection. Further examination identified potential perforations in the heat exchanger with visible rust staining along seams. Documented defective components with photos. Furnace requires both control board replacement and heat exchanger evaluation. Customer advised of repair options and replacement recommendation due to equipment age and condition. Responded to no-heat complaint on 12-year-old Lennox furnace. Diagnostic revealed error codes HA478 and E126, with circuit board failure evident upon inspection. Further examination identified potential perforations in the heat exchanger with visible rust staining along seams. Documented defective components with photos. Furnace requires both control board replacement and heat exchanger evaluation. Customer advised of repair options and replacement recommendation due to equipment age and condition.

Shawn G.

Shawn G. Job Checkin

Successfully replaced customer-supplied kitchen faucet along with installing new shut-off valves to replace the 30+ year old ones. Rebuilt drain system with new PVC piping, properly connecting all components with primer at joints and installing P-trap configuration to ensure proper drainage and eliminate the previous pieced-together appearance.

Successfully replaced customer-supplied kitchen faucet along with installing new shut-off valves to replace the 30+ year old ones. Rebuilt drain system with new PVC piping, properly connecting all components with primer at joints and installing P-trap configuration to ensure proper drainage and eliminate the previous pieced-together appearance. Successfully replaced customer-supplied kitchen faucet along with installing new shut-off valves to replace the 30+ year old ones. Rebuilt drain system with new PVC piping, properly connecting all components with primer at joints and installing P-trap configuration to ensure proper drainage and eliminate the previous pieced-together appearance.

Ethan S.

Ethan S. Job Checkin

Performed annual furnace tune-up on 15-year-old FRP system. Inspected heat exchanger, verified electrical components within specifications, and confirmed proper gas pressure with 55-degree temperature rise during operational testing. Noted inducer motor showing signs of noise - customer advised and estimate provided; system currently functioning normally with clean filter and balanced blower.

Performed annual furnace tune-up on 15-year-old FRP system. Inspected heat exchanger, verified electrical components within specifications, and confirmed proper gas pressure with 55-degree temperature rise during operational testing. Noted inducer motor showing signs of noise - customer advised and estimate provided; system currently functioning normally with clean filter and balanced blower. Performed annual furnace tune-up on 15-year-old FRP system. Inspected heat exchanger, verified electrical components within specifications, and confirmed proper gas pressure with 55-degree temperature rise during operational testing. Noted inducer motor showing signs of noise - customer advised and estimate provided; system currently functioning normally with clean filter and balanced blower.

Colten C.

Colten C. Job Checkin

Performed scheduled furnace tune-up on aging Goodman unit. Identified multiple critical issues including severely corroded flame sensor (cleaned temporarily), deteriorated burners, cracked collector box, and non-functioning inducer motor. Heat exchanger appears intact. After consultation with homeowner, unit has been recommended for complete replacement due to extensive component failure and overall condition.

Performed scheduled furnace tune-up on aging Goodman unit. Identified multiple critical issues including severely corroded flame sensor (cleaned temporarily), deteriorated burners, cracked collector box, and non-functioning inducer motor. Heat exchanger appears intact. After consultation with homeowner, unit has been recommended for complete replacement due to extensive component failure and overall condition. Performed scheduled furnace tune-up on aging Goodman unit. Identified multiple critical issues including severely corroded flame sensor (cleaned temporarily), deteriorated burners, cracked collector box, and non-functioning inducer motor. Heat exchanger appears intact. After consultation with homeowner, unit has been recommended for complete replacement due to extensive component failure and overall condition.

Mike B.

Mike B. Job Checkin

Performed comprehensive tune-up service on 21-year-old oil furnace. Replaced nozzle and oil filter, inspected heat exchanger and all components for defects, and verified proper operation. System is functioning correctly and remains in good condition despite age.

Performed comprehensive tune-up service on 21-year-old oil furnace. Replaced nozzle and oil filter, inspected heat exchanger and all components for defects, and verified proper operation. System is functioning correctly and remains in good condition despite age.

Mike B.

Mike B. Job Checkin

Performed annual furnace tune-up under Rewards agreement on wall-mounted heating unit. Identified pilot light failure and discovered spider crack in heat exchanger during inspection. Mini-split service was declined by customer. Completed condenser washing. Scheduled advisor follow-up for replacement heater pricing options.

Performed annual furnace tune-up under Rewards agreement on wall-mounted heating unit. Identified pilot light failure and discovered spider crack in heat exchanger during inspection. Mini-split service was declined by customer. Completed condenser washing. Scheduled advisor follow-up for replacement heater pricing options. Performed annual furnace tune-up under Rewards agreement on wall-mounted heating unit. Identified pilot light failure and discovered spider crack in heat exchanger during inspection. Mini-split service was declined by customer. Completed condenser washing. Scheduled advisor follow-up for replacement heater pricing options.

Shawn G.

Shawn G. Job Checkin

Investigated kitchen faucet with low pressure issue. Identified clog at adapter between hose and faucet under sink. Removed component, performed thorough cleaning of obstruction, reinstalled adapter, and verified proper water pressure restoration through functional testing.

Investigated kitchen faucet with low pressure issue. Identified clog at adapter between hose and faucet under sink. Removed component, performed thorough cleaning of obstruction, reinstalled adapter, and verified proper water pressure restoration through functional testing. Investigated kitchen faucet with low pressure issue. Identified clog at adapter between hose and faucet under sink. Removed component, performed thorough cleaning of obstruction, reinstalled adapter, and verified proper water pressure restoration through functional testing.

Andrew E.

Andrew E. Job Checkin

Plumbing Repair: I stopped a persistent leak under a kitchen sink by replacing a degraded washer and reseating the valve stem. After completing the repair, I pressure-tested the line and ensured watertight seals to prevent future issues.