Jarrod S.

Jarrod S. Job Checkin

Responded to service call for frozen sump pump discharge line with seal rupture. Inspected system to identify water source issues, drained the pump basket to restore functionality, and examined the discharge pipe connection which showed signs of wear. Recommended insulation for the exterior discharge line to prevent future freezing.

Responded to service call for frozen sump pump discharge line with seal rupture. Inspected system to identify water source issues, drained the pump basket to restore functionality, and examined the discharge pipe connection which showed signs of wear. Recommended insulation for the exterior discharge line to prevent future freezing. Responded to service call for frozen sump pump discharge line with seal rupture. Inspected system to identify water source issues, drained the pump basket to restore functionality, and examined the discharge pipe connection which showed signs of wear. Recommended insulation for the exterior discharge line to prevent future freezing.

Jared R.

Jared R. Job Checkin

Diagnosed electrical issue with recently installed IBC boiler that was causing repeated circuit breaker trips. Found defective neutral connection with 120V present on L1 to ground but no voltage from hot to neutral. Restored proper electrical connections, verified system operation, and confirmed stable heating function for in-law suite.

Diagnosed electrical issue with recently installed IBC boiler that was causing repeated circuit breaker trips. Found defective neutral connection with 120V present on L1 to ground but no voltage from hot to neutral. Restored proper electrical connections, verified system operation, and confirmed stable heating function for in-law suite. Diagnosed electrical issue with recently installed IBC boiler that was causing repeated circuit breaker trips. Found defective neutral connection with 120V present on L1 to ground but no voltage from hot to neutral. Restored proper electrical connections, verified system operation, and confirmed stable heating function for in-law suite.

Roger M.

Roger M. Job Checkin

Responded to no heat complaint for 2016 natural gas furnace. Diagnosed low flame sensor reading causing system failure. Performed maintenance including cleaning of flame sensor and inspection of gas orifice for blockage. System successfully restored to proper heating operation.

Responded to no heat complaint for 2016 natural gas furnace. Diagnosed low flame sensor reading causing system failure. Performed maintenance including cleaning of flame sensor and inspection of gas orifice for blockage. System successfully restored to proper heating operation. Responded to no heat complaint for 2016 natural gas furnace. Diagnosed low flame sensor reading causing system failure. Performed maintenance including cleaning of flame sensor and inspection of gas orifice for blockage. System successfully restored to proper heating operation.

Jon W

Jon W Job Checkin

Responded to service call for IBC boiler that was non-operational. Diagnosed issue as tripped circuit breaker. Reset breaker, which restored power to unit, and verified boiler returned to full operational status. System now functioning properly with normal operating temperatures (supply: 78°F, return: 75°F) and inlet pressure (16.9psi).

Responded to service call for IBC boiler that was non-operational. Diagnosed issue as tripped circuit breaker. Reset breaker, which restored power to unit, and verified boiler returned to full operational status. System now functioning properly with normal operating temperatures (supply: 78°F, return: 75°F) and inlet pressure (16.9psi). Responded to service call for IBC boiler that was non-operational. Diagnosed issue as tripped circuit breaker. Reset breaker, which restored power to unit, and verified boiler returned to full operational status. System now functioning properly with normal operating temperatures (supply: 78°F, return: 75°F) and inlet pressure (16.9psi).

Roger M.

Roger M. Job Checkin

Responded to a no-heat call for a 5-year-old furnace system. Diagnostic inspection revealed a clogged air filter causing system restriction. Removed and replaced filter, which restored normal heating operation. System functioning properly upon completion of service.

Responded to a no-heat call for a 5-year-old furnace system. Diagnostic inspection revealed a clogged air filter causing system restriction. Removed and replaced filter, which restored normal heating operation. System functioning properly upon completion of service. Responded to a no-heat call for a 5-year-old furnace system. Diagnostic inspection revealed a clogged air filter causing system restriction. Removed and replaced filter, which restored normal heating operation. System functioning properly upon completion of service.

Scott N

Scott N Job Checkin

Responded to a water leak complaint originating from upstairs bathroom shower and extending to basement. Diagnostic inspection revealed water intrusion through ceiling when bathtub/shower was in use. Located defective tub waste and overflow assembly. Successfully replaced tub waste and overflow components, effectively resolving the leak issue.

Responded to a water leak complaint originating from upstairs bathroom shower and extending to basement. Diagnostic inspection revealed water intrusion through ceiling when bathtub/shower was in use. Located defective tub waste and overflow assembly. Successfully replaced tub waste and overflow components, effectively resolving the leak issue. Responded to a water leak complaint originating from upstairs bathroom shower and extending to basement. Diagnostic inspection revealed water intrusion through ceiling when bathtub/shower was in use. Located defective tub waste and overflow assembly. Successfully replaced tub waste and overflow components, effectively resolving the leak issue.

Ali T

Ali T Job Checkin

Replaced ignitor and spark rod along with venturi on furnace. Identified seized gas line to gas valve and complete loss of pressure indicating heat exchanger failure. System inspection revealed significant oxidation and corrosion on copper components, particularly at connection points. Recommended consultation with comfort advisor for complete system replacement.

Replaced ignitor and spark rod along with venturi on furnace. Identified seized gas line to gas valve and complete loss of pressure indicating heat exchanger failure. System inspection revealed significant oxidation and corrosion on copper components, particularly at connection points. Recommended consultation with comfort advisor for complete system replacement. Replaced ignitor and spark rod along with venturi on furnace. Identified seized gas line to gas valve and complete loss of pressure indicating heat exchanger failure. System inspection revealed significant oxidation and corrosion on copper components, particularly at connection points. Recommended consultation with comfort advisor for complete system replacement.

Moe R.

Moe R. Job Checkin

Performed tune-up service on 12-year-old IBC boiler. Removed igniter to inspect heat exchanger, finding significant scale buildup and rust on inner walls. Determined igniter is worn and requires replacement. Discussed options with customer including cleaning (with risk of damage due to existing rust), heat exchanger replacement, or full boiler replacement. Customer elected to schedule follow-up consultation with service advisor.

Performed tune-up service on 12-year-old IBC boiler. Removed igniter to inspect heat exchanger, finding significant scale buildup and rust on inner walls. Determined igniter is worn and requires replacement. Discussed options with customer including cleaning (with risk of damage due to existing rust), heat exchanger replacement, or full boiler replacement. Customer elected to schedule follow-up consultation with service advisor. Performed tune-up service on 12-year-old IBC boiler. Removed igniter to inspect heat exchanger, finding significant scale buildup and rust on inner walls. Determined igniter is worn and requires replacement. Discussed options with customer including cleaning (with risk of damage due to existing rust), heat exchanger replacement, or full boiler replacement. Customer elected to schedule follow-up consultation with service advisor.

Moe R.

Moe R. Job Checkin

Responded to service call for IBC boiler CK199 reporting high vent limit error code and no hot water. Inspected venting system which showed proper condition, slope and clear termination. Diagnostic testing included running hot water for extended period while monitoring stack temperature, which remained below 127°F. Verified proper operation of exhaust temperature sensor, condensate drainage system, and central heating functionality. No current operational issues detected; likely caused by heavy hot water demand. Instructed customer on proper boiler reset procedure.

Responded to service call for IBC boiler CK199 reporting high vent limit error code and no hot water. Inspected venting system which showed proper condition, slope and clear termination. Diagnostic testing included running hot water for extended period while monitoring stack temperature, which remained below 127°F. Verified proper operation of exhaust temperature sensor, condensate drainage system, and central heating functionality. No current operational issues detected; likely caused by heavy hot water demand. Instructed customer on proper boiler reset procedure. Responded to service call for IBC boiler CK199 reporting high vent limit error code and no hot water. Inspected venting system which showed proper condition, slope and clear termination. Diagnostic testing included running hot water for extended period while monitoring stack temperature, which remained below 127°F. Verified proper operation of exhaust temperature sensor, condensate drainage system, and central heating functionality. No current operational issues detected; likely caused by heavy hot water demand. Instructed customer on proper boiler reset procedure.

Craig M.

Craig M. Job Checkin

Responded to service call for 2013 IBC boiler with no heat, exhibiting similar issues as previous visit. Upon inspection, detected gas odor during ignition failure. Removed spark ignitor, found it loose in ceramic housing, cleaned and properly realigned it. Upon reinstallation, boiler successfully fired up. Recommended future service to include replacement of spark ignitor, gas valve, and heat exchanger cleaning.

Responded to service call for 2013 IBC boiler with no heat, exhibiting similar issues as previous visit. Upon inspection, detected gas odor during ignition failure. Removed spark ignitor, found it loose in ceramic housing, cleaned and properly realigned it. Upon reinstallation, boiler successfully fired up. Recommended future service to include replacement of spark ignitor, gas valve, and heat exchanger cleaning. Responded to service call for 2013 IBC boiler with no heat, exhibiting similar issues as previous visit. Upon inspection, detected gas odor during ignition failure. Removed spark ignitor, found it loose in ceramic housing, cleaned and properly realigned it. Upon reinstallation, boiler successfully fired up. Recommended future service to include replacement of spark ignitor, gas valve, and heat exchanger cleaning.

Xavier C.

Xavier C. Job Checkin

Diagnosed 2013 IBC boiler that was short cycling and failing to ignite properly. Found significant corrosion on ignitor, uncleaned heat exchanger, and unit producing banging noise during startup. Determined heat exchanger and gas valve require replacement to resolve issues.

Diagnosed 2013 IBC boiler that was short cycling and failing to ignite properly. Found significant corrosion on ignitor, uncleaned heat exchanger, and unit producing banging noise during startup. Determined heat exchanger and gas valve require replacement to resolve issues. Diagnosed 2013 IBC boiler that was short cycling and failing to ignite properly. Found significant corrosion on ignitor, uncleaned heat exchanger, and unit producing banging noise during startup. Determined heat exchanger and gas valve require replacement to resolve issues.

Moe R.

Moe R. Job Checkin

Successfully completed warranty replacement of inducer motor and gas valve on heating system. Performed comprehensive testing including combustion analysis, temperature differential measurement, and leak check. All components now functioning according to manufacturer specifications with proper operation verified.

Successfully completed warranty replacement of inducer motor and gas valve on heating system. Performed comprehensive testing including combustion analysis, temperature differential measurement, and leak check. All components now functioning according to manufacturer specifications with proper operation verified. Successfully completed warranty replacement of inducer motor and gas valve on heating system. Performed comprehensive testing including combustion analysis, temperature differential measurement, and leak check. All components now functioning according to manufacturer specifications with proper operation verified.

Jared R.

Jared R. Job Checkin

Diagnosed boiler operating abnormally with flame fluctuations and vibration noise at intake pipe. Inspection revealed damaged ignitor at spark point and internal damage to the Venturi damper section affecting airflow and causing noise. Ordered replacement parts including ignitor, flame sensor, and gas valve assembly with attached Venturi.

Diagnosed boiler operating abnormally with flame fluctuations and vibration noise at intake pipe. Inspection revealed damaged ignitor at spark point and internal damage to the Venturi damper section affecting airflow and causing noise. Ordered replacement parts including ignitor, flame sensor, and gas valve assembly with attached Venturi. Diagnosed boiler operating abnormally with flame fluctuations and vibration noise at intake pipe. Inspection revealed damaged ignitor at spark point and internal damage to the Venturi damper section affecting airflow and causing noise. Ordered replacement parts including ignitor, flame sensor, and gas valve assembly with attached Venturi.

Roger M.

Roger M. Job Checkin

Responded to service call for furnace not heating properly. Diagnosed failed inducer motor causing pressure switch issues. Replaced inducer assembly due to age and operational failure. System now cycling properly and producing heat.

Responded to service call for furnace not heating properly. Diagnosed failed inducer motor causing pressure switch issues. Replaced inducer assembly due to age and operational failure. System now cycling properly and producing heat.

Jon W

Jon W Job Checkin

Responded to customer complaint of boiler experiencing flame fluctuations and vibration noise in the intake pipe, similar to previous issue addressed last year. Visual inspection revealed potential Venturi issue causing the rattling sound. Due to specialized tooling requirements needed for proper disassembly and repair, service has been rescheduled for a follow-up visit with appropriate equipment.

Responded to customer complaint of boiler experiencing flame fluctuations and vibration noise in the intake pipe, similar to previous issue addressed last year. Visual inspection revealed potential Venturi issue causing the rattling sound. Due to specialized tooling requirements needed for proper disassembly and repair, service has been rescheduled for a follow-up visit with appropriate equipment. Responded to customer complaint of boiler experiencing flame fluctuations and vibration noise in the intake pipe, similar to previous issue addressed last year. Visual inspection revealed potential Venturi issue causing the rattling sound. Due to specialized tooling requirements needed for proper disassembly and repair, service has been rescheduled for a follow-up visit with appropriate equipment.