Roger M.

Roger M. Job Checkin

Responded to no heat call for 10+ year old FA furnace. Diagnosed clogged condensate drain line causing system shutdown. Cleaned drain line and inspected heat exchanger, noting moderate corrosion and rust formation. System restored to proper operation after service.

Responded to no heat call for 10+ year old FA furnace. Diagnosed clogged condensate drain line causing system shutdown. Cleaned drain line and inspected heat exchanger, noting moderate corrosion and rust formation. System restored to proper operation after service. Responded to no heat call for 10+ year old FA furnace. Diagnosed clogged condensate drain line causing system shutdown. Cleaned drain line and inspected heat exchanger, noting moderate corrosion and rust formation. System restored to proper operation after service.

Roger M.

Roger M. Job Checkin

Completed non-member furnace tune-up service requested by customer referral from Charlie. Performed diagnostic testing with digital meter on electrical components and inspected system illumination. All systems functioning properly with no issues identified.

Completed non-member furnace tune-up service requested by customer referral from Charlie. Performed diagnostic testing with digital meter on electrical components and inspected system illumination. All systems functioning properly with no issues identified. Completed non-member furnace tune-up service requested by customer referral from Charlie. Performed diagnostic testing with digital meter on electrical components and inspected system illumination. All systems functioning properly with no issues identified.

Scott N

Scott N Job Checkin

Completed installation of customer-supplied sink, faucet, basket strainer and P-trap assembly in laundry room. Properly connected new fixtures to existing plumbing lines and verified operation with no leaks.

Completed installation of customer-supplied sink, faucet, basket strainer and P-trap assembly in laundry room. Properly connected new fixtures to existing plumbing lines and verified operation with no leaks. Completed installation of customer-supplied sink, faucet, basket strainer and P-trap assembly in laundry room. Properly connected new fixtures to existing plumbing lines and verified operation with no leaks.

Charles P.

Charles P. Job Checkin

Replaced four bathroom sink shut off valves (two hot and two cold) and tightened connecting nuts to ensure proper function and prevent leaks.

Replaced four bathroom sink shut off valves (two hot and two cold) and tightened connecting nuts to ensure proper function and prevent leaks. Replaced four bathroom sink shut off valves (two hot and two cold) and tightened connecting nuts to ensure proper function and prevent leaks.

Ali T

Ali T Job Checkin

Responded to no heat call for 9-year-old furnace. Diagnostic inspection revealed significant buildup in secondary heat exchanger and collector box, along with worn motors and ignition components. Performed thorough system evaluation including video inspection of internal components. Based on multiple component failures and system age, recommended either complete system replacement or major component overhaul to restore proper heating functionality.

Responded to no heat call for 9-year-old furnace. Diagnostic inspection revealed significant buildup in secondary heat exchanger and collector box, along with worn motors and ignition components. Performed thorough system evaluation including video inspection of internal components. Based on multiple component failures and system age, recommended either complete system replacement or major component overhaul to restore proper heating functionality. Responded to no heat call for 9-year-old furnace. Diagnostic inspection revealed significant buildup in secondary heat exchanger and collector box, along with worn motors and ignition components. Performed thorough system evaluation including video inspection of internal components. Based on multiple component failures and system age, recommended either complete system replacement or major component overhaul to restore proper heating functionality.

Chase O.

Chase O. Job Checkin

Successfully replaced customer-supplied kitchen faucet with proper installation of drain and water supply lines. Verified connections at P-trap assembly and ensured no leaks upon completion and testing.

Successfully replaced customer-supplied kitchen faucet with proper installation of drain and water supply lines. Verified connections at P-trap assembly and ensured no leaks upon completion and testing. Successfully replaced customer-supplied kitchen faucet with proper installation of drain and water supply lines. Verified connections at P-trap assembly and ensured no leaks upon completion and testing.

Jared R.

Jared R. Job Checkin

Responded to service call for an NTI combi boiler providing lukewarm domestic hot water despite adequate space heating functionality. Diagnosed issue with domestic water side of unit, performed full flush of holding tank to remove potential mineral buildup or sediment. After refilling and allowing proper heating cycle, system now producing appropriate hot water temperatures for all household fixtures.

Responded to service call for an NTI combi boiler providing lukewarm domestic hot water despite adequate space heating functionality. Diagnosed issue with domestic water side of unit, performed full flush of holding tank to remove potential mineral buildup or sediment. After refilling and allowing proper heating cycle, system now producing appropriate hot water temperatures for all household fixtures. Responded to service call for an NTI combi boiler providing lukewarm domestic hot water despite adequate space heating functionality. Diagnosed issue with domestic water side of unit, performed full flush of holding tank to remove potential mineral buildup or sediment. After refilling and allowing proper heating cycle, system now producing appropriate hot water temperatures for all household fixtures.

Jon W

Jon W Job Checkin

Responded to warranty call for malfunctioning furnace. Diagnosed faulty RDS board and confirmed need for 27A02 NON-Comm board replacement. After installation, verified system operation with control board showing proper functionality as evidenced by illuminated green indicator light. Furnace is now fully operational.

Responded to warranty call for malfunctioning furnace. Diagnosed faulty RDS board and confirmed need for 27A02 NON-Comm board replacement. After installation, verified system operation with control board showing proper functionality as evidenced by illuminated green indicator light. Furnace is now fully operational.

Tim M.

Tim M. Job Checkin

Successfully replaced a leaking 75-gallon natural gas power vent water heater due to tank failure. Installation included proper connection of copper lines, venting system, and all required valves. Bradford White unit was installed and tested to ensure proper operation.

Successfully replaced a leaking 75-gallon natural gas power vent water heater due to tank failure. Installation included proper connection of copper lines, venting system, and all required valves. Bradford White unit was installed and tested to ensure proper operation. Successfully replaced a leaking 75-gallon natural gas power vent water heater due to tank failure. Installation included proper connection of copper lines, venting system, and all required valves. Bradford White unit was installed and tested to ensure proper operation.

Roger M.

Roger M. Job Checkin

Responded to heating issue where furnace was not maintaining temperature or auto-activating at set point (69°). Diagnosed system with dirty filter restricting airflow. Replaced air filter to restore proper system function and air circulation.

Responded to heating issue where furnace was not maintaining temperature or auto-activating at set point (69°). Diagnosed system with dirty filter restricting airflow. Replaced air filter to restore proper system function and air circulation. Responded to heating issue where furnace was not maintaining temperature or auto-activating at set point (69°). Diagnosed system with dirty filter restricting airflow. Replaced air filter to restore proper system function and air circulation.

Roger M.

Roger M. Job Checkin

Replaced failed PSC draft combustion inducer blower assembly on customer's furnace. Completed installation of new inducer motor assembly and verified proper operation. Post-repair combustion analysis with Testo 310 confirmed optimal performance with 97.2% efficiency, CO2 at 8 ppm, and CO at 5 ppm.

Replaced failed PSC draft combustion inducer blower assembly on customer's furnace. Completed installation of new inducer motor assembly and verified proper operation. Post-repair combustion analysis with Testo 310 confirmed optimal performance with 97.2% efficiency, CO2 at 8 ppm, and CO at 5 ppm. Replaced failed PSC draft combustion inducer blower assembly on customer's furnace. Completed installation of new inducer motor assembly and verified proper operation. Post-repair combustion analysis with Testo 310 confirmed optimal performance with 97.2% efficiency, CO2 at 8 ppm, and CO at 5 ppm.

Roger M.

Roger M. Job Checkin

Responded to no-heat call for furnace of indeterminate age. Diagnosed dirty flame sensor causing system failure. Cleaned flame sensor and replaced air filter, restoring proper heating function.

Responded to no-heat call for furnace of indeterminate age. Diagnosed dirty flame sensor causing system failure. Cleaned flame sensor and replaced air filter, restoring proper heating function. Responded to no-heat call for furnace of indeterminate age. Diagnosed dirty flame sensor causing system failure. Cleaned flame sensor and replaced air filter, restoring proper heating function.

Koshoua V.

Koshoua V. Job Checkin

Performed diagnostic inspection on furnace system after reports of temperature inconsistency and airflow issues in multiple rooms. Conducted visual inspection of ductwork using camera equipment, confirming no blockages present. Tested all damper motors and discovered air leakage occurring even when dampers were closed. Identified significant heat loss from multiple sliding doors (8 upstairs, 4 downstairs) contributing to temperature regulation problems. Closed unused vents to improve airflow distribution and recommended installation of zone panel system for better temperature control, particularly for basement-only operation as requested by homeowner.

Performed diagnostic inspection on furnace system after reports of temperature inconsistency and airflow issues in multiple rooms. Conducted visual inspection of ductwork using camera equipment, confirming no blockages present. Tested all damper motors and discovered air leakage occurring even when dampers were closed. Identified significant heat loss from multiple sliding doors (8 upstairs, 4 downstairs) contributing to temperature regulation problems. Closed unused vents to improve airflow distribution and recommended installation of zone panel system for better temperature control, particularly for basement-only operation as requested by homeowner. Performed diagnostic inspection on furnace system after reports of temperature inconsistency and airflow issues in multiple rooms. Conducted visual inspection of ductwork using camera equipment, confirming no blockages present. Tested all damper motors and discovered air leakage occurring even when dampers were closed. Identified significant heat loss from multiple sliding doors (8 upstairs, 4 downstairs) contributing to temperature regulation problems. Closed unused vents to improve airflow distribution and recommended installation of zone panel system for better temperature control, particularly for basement-only operation as requested by homeowner.

Koshoua V.

Koshoua V. Job Checkin

Performed diagnostic inspection on non-operational Trane furnace (2005). Identified two critical issues: gas valve was stuck closed/faulty and confirmed heat exchanger has developed a crack (visible corrosion along seam). Informed homeowner that unit requires either complete furnace replacement or heat exchanger replacement to restore proper operation and ensure safety.

Performed diagnostic inspection on non-operational Trane furnace (2005). Identified two critical issues: gas valve was stuck closed/faulty and confirmed heat exchanger has developed a crack (visible corrosion along seam). Informed homeowner that unit requires either complete furnace replacement or heat exchanger replacement to restore proper operation and ensure safety. Performed diagnostic inspection on non-operational Trane furnace (2005). Identified two critical issues: gas valve was stuck closed/faulty and confirmed heat exchanger has developed a crack (visible corrosion along seam). Informed homeowner that unit requires either complete furnace replacement or heat exchanger replacement to restore proper operation and ensure safety.

Ali T

Ali T Job Checkin

Responded to no-heat service call for 20-year-old zoning system with heating issues in multiple zones. Diagnosed faulty zone control components and aging thermostats. Replaced one defective thermostat to restore proper zone temperature control. System operational upon completion.

Responded to no-heat service call for 20-year-old zoning system with heating issues in multiple zones. Diagnosed faulty zone control components and aging thermostats. Replaced one defective thermostat to restore proper zone temperature control. System operational upon completion. Responded to no-heat service call for 20-year-old zoning system with heating issues in multiple zones. Diagnosed faulty zone control components and aging thermostats. Replaced one defective thermostat to restore proper zone temperature control. System operational upon completion.