Responded to service call for HTP boiler shutdown issue. Diagnosed E29 error code indicating faulty pressure switch. Found pressure switch incorrectly remaining closed when inducer motor not running (should be normally open). Reset boiler for temporary operation and cleaned spiderwebs from intake vent. Recommended replacement of pressure switch for permanent resolution.