Performed geothermal system maintenance per membership agreement. Diagnosed system locked out on low pressure fault code. Tested pressure sensor continuity and performed board jump test - both confirmed control board failure rather than actual low pressure condition. Arranged for replacement control board to be ordered through Parts department, noting potential warranty coverage.

Performed geothermal system maintenance per membership agreement. Diagnosed system locked out on low pressure fault code. Tested pressure sensor continuity and performed board jump test - both confirmed control board failure rather than actual low pressure condition. Arranged for replacement control board to be ordered through Parts department, noting potential warranty coverage. Performed geothermal system maintenance per membership agreement. Diagnosed system locked out on low pressure fault code. Tested pressure sensor continuity and performed board jump test - both confirmed control board failure rather than actual low pressure condition. Arranged for replacement control board to be ordered through Parts department, noting potential warranty coverage.