Responded to customer complaint regarding gas burner ignition failure on outdoor wood/gas central boiler system. Diagnostic inspection revealed proper burner starting sequence but insufficient gas pressure. Determined that customer's 100lb LP tank with low-pressure regulator cannot provide adequate pressure through the underground line. Advised customer to upgrade to minimum 250-gallon LP tank with appropriate regulators to resolve the issue.