I am a home service technician, and I recently completed a job at a client's home. The client reported that their air conditioning unit was not cooling, and after arriving at the scene, I discovered that the capacitor outside had been fried. I replaced the capacitor and the unit fired up. The liquid line temperature was 131°, so I cleaned off the outdoor condenser and got it down to 86°. The client was cooling at the time of service.