Responded to service call for inoperative RTU that was installed approximately 3 years ago. Unit was attempting to fire but failing, displaying 9 flashes followed by ignition lockout code. Diagnostic testing revealed limit code error. All limits were tested and confirmed operational. Voltage measurement showed proper 27V at limit terminal, but board was not recognizing input signal. Control board was replaced to resolve the issue.