Unit not cooling. Contactor would pull in condenser fan would run but compressor wouldn’t kick on. Checked voltage had proper voltage. Checked mfd on capacitor and it was reading low. Tired getting compressor to kick on with new capacitor and hard start but it still didn’t run. Let customer know I recommend replacing system. Would like an estimate on compressor replacement and new unit.